TABLES |
Mesure
units |
|
|
Fluid
mechanic |
|
|
|
|
|

|
|
Pressure: |
Atmospheric pressure at 1,01325
bar, i.e. normal atmospheric pressure on the sea level at
0°C. |
Density: |
Ratio of
the mass of water (kg) occupied in a volume of 1 m3. |
Specific enthalpy: |
Sensible Heat, it is the
quantity of heat contained in 1 kg of water according to the
selected temperature. |
Specific heat: |
Quantity of heat necessary to increase
the temperature of a 1° Celsius per unit of mass of 1 kg of
water. |
Volume heat capacity: |
Quantity of heat necessary to increase the temperature
of a 1° Celsius on a unit of volume of 1 m3 of water. |
Dynamic viscosity: |
The viscosity of a fluid characterizes
the resistance to the movement of the fluid. |
NB: Energy values in kcal/kg are given on a basis
of 4.1868 J .Values not normally used.
Temperature
|
Pressure
|
Saturation vapor pressure
|
Density
|
Specific enthalpy of liquid water
|
Specific heat
|
Volume heat capacity
|
Dynamic viscosity
|
°C
|
Pa
|
Pa
|
kg/m3
|
kj/kg
|
kcal/kg
|
kj/kg.K
|
kcal/kg.K
|
kj/m3
|
kg/m.s
|
0.00
|
101325
|
611
|
999.82
|
0.06
|
0.01
|
4.217
|
1.007
|
4216.10
|
0.001792
|
1.00
|
101325
|
657
|
999.89
|
4.28
|
1.02
|
4.213
|
1.006
|
4213.03
|
0.001731
|
2.00
|
101325
|
705
|
999.94
|
8.49
|
2.03
|
4.210
|
1.006
|
4210.12
|
0.001674
|
3.00
|
101325
|
757
|
999.98
|
12.70
|
3.03
|
4.207
|
1.005
|
4207.36
|
0.001620
|
4.00
|
101325
|
813
|
1000.00
|
16.90
|
4.04
|
4.205
|
1.004
|
4204.74
|
0.001569
|
5.00
|
101325
|
872
|
1000.00
|
21.11
|
5.04
|
4.202
|
1.004
|
4202.26
|
0.001520
|
6.00
|
101325
|
935
|
999.99
|
25.31
|
6.04
|
4.200
|
1.003
|
4199.89
|
0.001473
|
7.00
|
101325
|
1001
|
999.96
|
29.51
|
7.05
|
4.198
|
1.003
|
4197.63
|
0.001429
|
8.00
|
101325
|
1072
|
999.91
|
33.70
|
8.05
|
4.196
|
1.002
|
4195.47
|
0.001386
|
9.00
|
101325
|
1147
|
999.85
|
37.90
|
9.05
|
4.194
|
1.002
|
4193.40
|
0.001346
|
10.00
|
101325
|
1227
|
999.77
|
42.09
|
10.05
|
4.192
|
1.001
|
4191.42
|
0.001308
|
11.00
|
101325
|
1312
|
999.68
|
46.28
|
11.05
|
4.191
|
1.001
|
4189.51
|
0.001271
|
12.00
|
101325
|
1402
|
999.58
|
50.47
|
12.06
|
4.189
|
1.001
|
4187.67
|
0.001236
|
13.00
|
101325
|
1497
|
999.46
|
54.66
|
13.06
|
4.188
|
1.000
|
4185.89
|
0.001202
|
14.00
|
101325
|
1597
|
999.33
|
58.85
|
14.06
|
4.187
|
1.000
|
4184.16
|
0.001170
|
15.00
|
101325
|
1704
|
999.19
|
63.04
|
15.06
|
4.186
|
1.000
|
4182.49
|
0.001139
|
16.00
|
101325
|
1817
|
999.03
|
67.22
|
16.06
|
4.185
|
1.000
|
4180.86
|
0.001109
|
17.00
|
101325
|
1936
|
998.86
|
71.41
|
17.06
|
4.184
|
0.999
|
4179.27
|
0.001081
|
18.00
|
101325
|
2063
|
998.68
|
75.59
|
18.05
|
4.183
|
0.999
|
4177.72
|
0.001054
|
19.00
|
101325
|
2196
|
998.49
|
79.77
|
19.05
|
4.182
|
0.999
|
4176.20
|
0.001028
|
20.00
|
101325
|
2337
|
998.29
|
83.95
|
20.05
|
4.182
|
0.999
|
4174.70
|
0.001003
|
21.00
|
101325
|
2486
|
998.08
|
88.14
|
21.05
|
4.181
|
0.999
|
4173.23
|
0.000979
|
22.00
|
101325
|
2642
|
997.86
|
92.32
|
22.05
|
4.181
|
0.999
|
4171.78
|
0.000955
|
23.00
|
101325
|
2808
|
997.62
|
96.50
|
23.05
|
4.180
|
0.998
|
4170.34
|
0.000933
|
24.00
|
101325
|
2982
|
997.38
|
100.68
|
24.05
|
4.180
|
0.998
|
4168.92
|
0.000911
|
25.00
|
101325
|
3166
|
997.13
|
104.86
|
25.04
|
4.180
|
0.998
|
4167.51
|
0.000891
|
26.00
|
101325
|
3360
|
996.86
|
109.04
|
26.04
|
4.179
|
0.998
|
4166.11
|
0.000871
|
27.00
|
101325
|
3564
|
996.59
|
113.22
|
27.04
|
4.179
|
0.998
|
4164.71
|
0.000852
|
28.00
|
101325
|
3779
|
996.31
|
117.39
|
28.04
|
4.179
|
0.998
|
4163.31
|
0.000833
|
29.00
|
101325
|
4004
|
996.02
|
121.57
|
29.04
|
4.179
|
0.998
|
4161.92
|
0.000815
|
30.00
|
101325
|
4242
|
995.71
|
125.75
|
30.04
|
4.178
|
0.998
|
4160.53
|
0.000798
|
31.00
|
101325
|
4491
|
995.41
|
129.93
|
31.03
|
4.178
|
0.998
|
4159.13
|
0.000781
|
32.00
|
101325
|
4754
|
995.09
|
134.11
|
32.03
|
4.178
|
0.998
|
4157.73
|
0.000765
|
33.00
|
101325
|
5029
|
994.76
|
138.29
|
33.03
|
4.178
|
0.998
|
4156.33
|
0.000749
|
34.00
|
101325
|
5318
|
994.43
|
142.47
|
34.03
|
4.178
|
0.998
|
4154.92
|
0.000734
|
35.00
|
101325
|
5622
|
994.08
|
146.64
|
35.03
|
4.178
|
0.998
|
4153.51
|
0.000720
|
36.00
|
101325
|
5940
|
993.73
|
150.82
|
36.02
|
4.178
|
0.998
|
4152.08
|
0.000705
|
37.00
|
101325
|
6274
|
993.37
|
155.00
|
37.02
|
4.178
|
0.998
|
4150.65
|
0.000692
|
38.00
|
101325
|
6624
|
993.00
|
159.18
|
38.02
|
4.178
|
0.998
|
4149.20
|
0.000678
|
39.00
|
101325
|
6991
|
992.63
|
163.36
|
39.02
|
4.179
|
0.998
|
4147.74
|
0.000666
|
40.00
|
101325
|
7375
|
992.25
|
167.54
|
40.02
|
4.179
|
0.998
|
4146.28
|
0.000653
|
41.00
|
101325
|
7777
|
991.86
|
171.71
|
41.01
|
4.179
|
0.998
|
4144.80
|
0.000641
|
42.00
|
101325
|
8198
|
991.46
|
175.89
|
42.01
|
4.179
|
0.998
|
4143.30
|
0.000629
|
43.00
|
101325
|
8639
|
991.05
|
180.07
|
43.01
|
4.179
|
0.998
|
4141.80
|
0.000618
|
44.00
|
101325
|
9100
|
990.64
|
184.25
|
44.01
|
4.179
|
0.998
|
4140.28
|
0.000607
|
45.00
|
101325
|
9582
|
990.22
|
188.43
|
45.01
|
4.180
|
0.998
|
4138.75
|
0.000596
|
46.00
|
101325
|
10085
|
989.80
|
192.61
|
46.00
|
4.180
|
0.998
|
4137.20
|
0.000586
|
47.00
|
101325
|
10612
|
989.36
|
196.79
|
47.00
|
4.180
|
0.998
|
4135.64
|
0.000576
|
48.00
|
101325
|
11161
|
988.92
|
200.97
|
48.00
|
4.180
|
0.998
|
4134.06
|
0.000566
|
49.00
|
101325
|
11735
|
988.47
|
205.15
|
49.00
|
4.181
|
0.999
|
4132.47
|
0.000556
|
50.00
|
101325
|
12335
|
988.02
|
209.33
|
50.00
|
4.181
|
0.999
|
4130.87
|
0.000547
|
51.00
|
101325
|
12960
|
987.56
|
213.51
|
51.00
|
4.181
|
0.999
|
4129.25
|
0.000538
|
52.00
|
101325
|
13612
|
987.09
|
217.69
|
52.00
|
4.182
|
0.999
|
4127.61
|
0.000529
|
53.00
|
101325
|
14292
|
986.62
|
221.88
|
52.99
|
4.182
|
0.999
|
4125.97
|
0.000521
|
54.00
|
101325
|
15001
|
986.14
|
226.06
|
53.99
|
4.182
|
0.999
|
4124.30
|
0.000512
|
55.00
|
101325
|
15740
|
985.65
|
230.24
|
54.99
|
4.183
|
0.999
|
4122.63
|
0.000504
|
56.00
|
101325
|
16510
|
985.16
|
234.42
|
55.99
|
4.183
|
0.999
|
4120.94
|
0.000496
|
57.00
|
101325
|
17312
|
984.66
|
238.61
|
56.99
|
4.183
|
0.999
|
4119.24
|
0.000489
|
58.00
|
101325
|
18146
|
984.16
|
242.79
|
57.99
|
4.184
|
0.999
|
4117.52
|
0.000481
|
59.00
|
101325
|
19015
|
983.64
|
246.97
|
58.99
|
4.184
|
0.999
|
4115.79
|
0.000474
|
60.00
|
101325
|
19919
|
983.13
|
251.16
|
59.99
|
4.185
|
0.999
|
4114.05
|
0.000467
|
61.00
|
101325
|
20859
|
982.60
|
255.34
|
60.99
|
4.185
|
1.000
|
4112.30
|
0.000460
|
62.00
|
101325
|
21837
|
982.07
|
259.53
|
61.99
|
4.186
|
1.000
|
4110.53
|
0.000453
|
63.00
|
101325
|
22854
|
981.54
|
263.72
|
62.99
|
4.186
|
1.000
|
4108.75
|
0.000447
|
64.00
|
101325
|
23910
|
981.00
|
267.90
|
63.99
|
4.187
|
1.000
|
4106.97
|
0.000440
|
65.00
|
101325
|
25008
|
980.45
|
272.09
|
64.99
|
4.187
|
1.000
|
4105.17
|
0.000434
|
66.00
|
101325
|
26148
|
979.90
|
276.28
|
65.99
|
4.188
|
1.000
|
4103.36
|
0.000428
|
67.00
|
101325
|
27332
|
979.34
|
280.46
|
66.99
|
4.188
|
1.000
|
4101.54
|
0.000422
|
68.00
|
101325
|
28561
|
978.78
|
284.65
|
67.99
|
4.189
|
1.000
|
4099.71
|
0.000416
|
69.00
|
101325
|
29837
|
978.21
|
288.84
|
68.99
|
4.189
|
1.001
|
4097.88
|
0.000410
|
70.00
|
101325
|
31161
|
977.63
|
293.03
|
69.99
|
4.190
|
1.001
|
4096.03
|
0.000404
|
71.00
|
101325
|
32533
|
977.05
|
297.22
|
70.99
|
4.190
|
1.001
|
4094.18
|
0.000399
|
72.00
|
101325
|
33957
|
976.47
|
301.41
|
71.99
|
4.191
|
1.001
|
4092.31
|
0.000394
|
73.00
|
101325
|
35433
|
975.88
|
305.60
|
72.99
|
4.192
|
1.001
|
4090.45
|
0.000388
|
74.00
|
101325
|
36963
|
975.28
|
309.79
|
73.99
|
4.192
|
1.001
|
4088.57
|
0.000383
|
75.00
|
101325
|
38548
|
974.68
|
313.99
|
74.99
|
4.193
|
1.001
|
4086.69
|
0.000378
|
76.00
|
101325
|
40190
|
974.08
|
318.18
|
76.00
|
4.194
|
1.002
|
4084.80
|
0.000373
|
77.00
|
101325
|
41890
|
973.46
|
322.37
|
77.00
|
4.194
|
1.002
|
4082.91
|
0.000369
|
78.00
|
101325
|
43650
|
972.85
|
326.57
|
78.00
|
4.195
|
1.002
|
4081.01
|
0.000364
|
79.00
|
101325
|
45473
|
972.23
|
330.76
|
79.00
|
4.196
|
1.002
|
4079.11
|
0.000359
|
80.00
|
101325
|
47359
|
971.60
|
334.96
|
80.00
|
4.196
|
1.002
|
4077.20
|
0.000355
|
81.00
|
101325
|
49310
|
970.97
|
339.16
|
81.01
|
4.197
|
1.002
|
4075.29
|
0.000351
|
82.00
|
101325
|
51328
|
970.33
|
343.35
|
82.01
|
4.198
|
1.003
|
4073.38
|
0.000346
|
83.00
|
101325
|
53415
|
969.69
|
347.55
|
83.01
|
4.199
|
1.003
|
4071.46
|
0.000342
|
84.00
|
101325
|
55572
|
969.04
|
351.75
|
84.01
|
4.200
|
1.003
|
4069.54
|
0.000338
|
85.00
|
101325
|
57803
|
968.39
|
355.95
|
85.02
|
4.200
|
1.003
|
4067.62
|
0.000334
|
86.00
|
101325
|
60107
|
967.73
|
360.15
|
86.02
|
4.201
|
1.003
|
4065.70
|
0.000330
|
87.00
|
101325
|
62488
|
967.07
|
364.35
|
87.02
|
4.202
|
1.004
|
4063.78
|
0.000326
|
88.00
|
101325
|
64947
|
966.41
|
368.56
|
88.03
|
4.203
|
1.004
|
4061.85
|
0.000322
|
89.00
|
101325
|
67486
|
965.74
|
372.76
|
89.03
|
4.204
|
1.004
|
4059.93
|
0.000319
|
90.00
|
101325
|
70108
|
965.06
|
376.96
|
90.04
|
4.205
|
1.004
|
4058.00
|
0.000315
|
91.00
|
101325
|
72814
|
964.38
|
381.17
|
91.04
|
4.206
|
1.005
|
4056.08
|
0.000311
|
92.00
|
101325
|
75607
|
963.70
|
385.38
|
92.05
|
4.207
|
1.005
|
4054.15
|
0.000308
|
93.00
|
101325
|
78488
|
963.01
|
389.58
|
93.05
|
4.208
|
1.005
|
4052.23
|
0.000304
|
94.00
|
101325
|
81460
|
962.31
|
393.79
|
94.06
|
4.209
|
1.005
|
4050.31
|
0.000301
|
95.00
|
101325
|
84525
|
961.62
|
398.00
|
95.06
|
4.210
|
1.006
|
4048.39
|
0.000298
|
96.00
|
101325
|
87685
|
960.91
|
402.21
|
96.07
|
4.211
|
1.006
|
4046.47
|
0.000295
|
97.00
|
101325
|
90943
|
960.20
|
406.42
|
97.07
|
4.212
|
1.006
|
4044.55
|
0.000291
|
98.00
|
101325
|
94301
|
959.49
|
410.64
|
98.08
|
4.213
|
1.006
|
4042.64
|
0.000288
|
99.00
|
101325
|
97760
|
958.78
|
414.85
|
99.09
|
4.214
|
1.007
|
4040.73
|
0.000285
|
100.00
|
101325
|
101325
|
958.05
|
419.06
|
100.09
|
4.216
|
1.007
|
4038.82
|
0.000282
|
Any recopy of this table on another website or in another form
of publication is completely forbidden.
Last update : June 2003
|
|