|
Calculs psychrométriques
The program makes it possible according of 2 elements of inputs
to know all the other parameters of a state of the humid air, which
is to say in function:
- Dry temperature and relative humidity
- Dry temperature and wet temperature.
- Dry temperature and specific moisture.
- Dry temperature and enthalpy.
- Relative humidity and specific moisture.
- Specific moisture and enthalpy.


The function of calculation of the temperature of the humid air
is done by iteration, i.e. successive approaches. The margin of
error can to be near of 0.1°C at most.
Cooling by adiabatic humidification
Cooling and humidification can be achieved by water spraying
in the air. One calls this "adiabatic process", provided
that there is neither contribution nor withdrawal of heat. This
phenomenon is also known under the name of evaporation cooling.
When the air unsaturated comes in contact with recycled spray
water, there is water evaporation, if the process is adequate,
the air will be saturated. If there is not contribution of heat
during this stage, heat necessary to the evaporation of water
can be provided only by the air, which results with a fall from
temperature from the air and to an increase in the relative
humidity. The total enthalpy of the humid air remains the same
one.
This is said "about humidifiers with constant enthalpy ",
such as:
- jet humidifiers of cold water (or " washers of air"),
- humidifiers by contact with cold water (fixed plate, wheel,
honeycomb),
- humidifiers by ultrasounds,

The calculation program makes it possible to carry out psychrometric
calculations of the air before vaporization and also the air after
cooling adiabatic according to hygrometric rate given.

Humidification by steam water injection
The steam humidifier is autonomous when it is equipped with an
autonomous vapor generator or not if it must be connected to a network
existing vapor. This process of isothermal humidification involves
an increase in the temperature locally.

By injecting steam water the temperature of the air vairy little.
However to determine with precision the psychrometric characteristics
of the air, it is necessary to carry out the calculation of
this temperature.
The calculation programme makes it possible to carry out psychrometric
calculations of the air before vaporization and also that the
air after vaporization of the vapor according to preset rate's
of hygroscopy and of the introduced water vapor.
Psychrometric calculation by mixture of air with constant
specific moisture

Weather data for thermal calculations
In program PYSCHROSI is integrated a library of the weather data
defining the climatic parameters adopted in general for the dimensioning
of the installations of air-conditioning.

General definitions
In air-conditioning, it is of use to work with the mass flow qm
(in kg/s or kg/h), because the volume flow qv (in m³/s or m³/h)
are variable according to the temperature (1 kg of air increases
in volume with the rise in temperature).
DRY TEMPERATURE in °C - Actual temperature of the humid
air observed using a thermometer or of a temperature gauge. It is
the temperature of the air indicated by a no affected thermometer
by the moisture of air.
WET TEMPERATURE in °C - It is the temperature recorded
by a thermometer where the bulb is covered with an impregnated water
wick. The wet temperatures are always lower than the dry temperatures
and the only case where they are identical is with a relative humidity
at 100%.
Adiabatic saturation temperature - Temperature to which
the humid air can be brought to adiabatic saturation by the evaporation
of water, i.e. at the wet temperature (no gain or loss of heat to
the environments)
DEW TEMPERATURE in °C - It is the temperature from which
the water vapor contained in the humid air starts to condense in
contact with a cold surface. During a cooling, specific moisture
and the partial pressure of the water vapor remain constant.
SPECIFIC HUMIDITE or absolute humidity or water content
- (Humidity ratio, moisture constant, mixing ratio, gold specific
humidity): It is the water mass (liquid, solid, vapor) contained
in one kg of dry air. This water weight remains constant when the
ambient temperature varies provided that it does not fall below
the dew temperature. If the temperature falls below dew point, part
of this water mass will condense in the form of droplets on the
coldest walls.
RELATIVE HUMIDITE in % - It is the ratio of the mass of
the water vapor contained in a certain quantity of humid air to
the vapor mass which it could contain if it were saturated at the
same temperature. To 100%, the air is completely saturated. To 50%,
the air contains half of what it could have if it were saturated
at the same temperature. When the water content reaches 100% the
formation of droplets of liquid occurs on the objects!
SPECIFIC VOLUME in m3/kg of air - It is the volume occupied
by the weight of one kilogram of dry air in a whole of specific
conditions.
DENSITY in kg/m3 of humid air: It is the mass of one m3
of humid air. The pressure of the mixture (dry air + water vapor)
is equal to the sum of the pressures would have each component if
it were alone to occupy the volume of the unit. Therefore in one
m3 of humid air, one finds the sum of the masses of components,
it is the sum of the density of the dry air and the water vapor,
with the partial pressures and indicated temperatures.
ENTHALPY - Total energy (heat) contained in the unit weight
of the humid air (By convention, regarded as no one at 0°C).
The enthalpy includes sensible heat and the latent heat contained
in the air.
SENSIBLE HEAT and LATENT HEAT - Sensible heat is
heat (energy) in the air due to the temperature of air. The latent
heat is heat (energy) in the air due to the moisture of air. After
this, the air with the same quantity of energy can be dry hot air
(high sensible heat) or refreshed humid air (high latent heat)
Vapor pressure - It is the pressure partial vapor in the
air. This pressure is the same as the saturating vapor pressure
at the dew temperature.
Saturating vapor pressure - It is the maximum vapor pressure
which the air can support (not supersaturated) at a given temperature.
The saturating vapor pressure increases with the temperature or
loss of heat to the environments)
Complementary definitions
SHF (Sensitive Heat Factor) - Ratio of sensible heat to
total heat
By-pass Factor: By-pass Factor is a function of the physical
characteristics of the coil and the operating conditions. It is
considered that it represents the percentage of air which passes
through the coil without undergoing some changes.
Adiabatic cooling: Cooling is carried out almost to the adiabatic
curves parallel of the psychrometric diagram. This cooling is called
"adiabatic cooling ". It is the case when water is brumisée
in fine droplets in a room, without there being contribution of
heat at the same time, the energy necessary to the evaporation of
this water is withdrawn at the ambient air.
Psychrometric functions
The functions below are used in the working file and can be re-used
on other worksheets of this same sorter.
These functions are written in Visual BASIC especially for Excel
Atmospheric pressure
in kPa
- Z = Altitude in m
Function = Patm(Z)
Pressure vapor
in kPa
- ts = dry temperature °C
- hr = relative humidity in %
Function = Psy_Pv(ts, Hr)
Pressure partial
vapor in kPa
- ts = dry temperature °C
- wet HT = temperature °C
- Z = Altitude in m
Function = Psy_Pvh(ts, HT, Z)
Pressure vapor
of saturation in kPa
- ts = dry temperature °C
Function = Psy_Pvs(ts)
Specific moisture
to saturation in kg / m3 of dry air
- ts = Dry température in °C
- Z = Altitude in m
Function = Psy_Hss(ts, Z)
Specific moisture
in kg / m3 of dry air
- ts = Dry temperature in °C
- Hr = relative Humidity
- Z = Altitude in m
Function = Psy_Hs(ts, Hr, Z)
Specific moisture
in kg / m3 of dry air
- ts = Dry temperature in °C
- H = Enthalpy in Kj/kg of dry air
Function = Psy_HsH(ts, H)
Relative humidity
in %
- ts = Dry temperature in °C
- Hs = Specific moisture in kg/kg of dry air
- Z = Altitude in m
Function = Psy_Hr(ts, Hs, Z)
Dry temperature
(°C)
- Pvs = Vapor pressure of saturation in kPa
Function = Psy_Ts(Pvs)
Dry temperature
(°C) according to H and Hs
- H = Enthalpy in Kj/kg of dry air
- Hs = Specific moisture in kg/kg of dry air
Function = Psy_TsH(H, Hs)
Dew temperature
(°C)
- Pv = Vapor pressure of saturation in kPa
Function = Psy_Tr(Pv)
Dew temperature
(°C)
- ts = Temperature dries in °C
- hr = Relative humidity in %
Function = Psy_Trosée(ts, Hr)
Enthalpy in Kj/kg
of dry air
- ts = Dry temperature in °C
- hr = Relative humidity in %
- Z = Altitude in m
Function = Psy_Enth(ts, Hr, Z)
Enthalpy in Kcal/kg
of dry air
- ts = Dry temperature in °C
- Hs = Specific moisture in kg/kg of dry air
Function = Psy_EnthKcal(ts, Hs)
Specific heat
of the dry air in kJ / kg K
- ts = Dry temperature in °C
Function = Psy_cpa(ts)
Specific heat
of moisture in kJ / kg K
- ts = Dry temperature in °C
Function = Psy_cpv(ts)
Latent heat of
vaporization at saturation in kJ/kg
- ts = Dry temperature in °C
Function = Psy_Hlp(ts)
Density in kg/m3
of humid air
- ts = Dry temperature in °C
- Hr = Relative humidity
- Z = Altitude in m
Function = Psy_M_vol(ts, Hr, Z)
Specific volume
in m3 of humid air / kg of dry air
- ts = Dry temperature in °C
- Hr = relative Humidity
- Z = Altitude in m
Function = Psy_V_mass(ts, Hr, Z)
Specific volume
in m3 of humid air / kg of humid air
- ts = Temperature dries in °C
- Hr = relative Humidity
- Z = Altitude in m
Function = Psy_V_ma_Humi(ts, Hr, Z)
Wet temperature
°C
- ts = Dry temperature in °C
- Hr = relative Humidity
- Z = Altitude in m
Function = Psy_th(ts, Hr, Z)
Adiabatic temperature (Calculation in adiabatic cooling)
- th = Wet-bulb
temperature °C
- Hr = relative Humidity
- Z = Altitude in m
Fonction =Psy_th1(th , Hr , Z) . (iterative Calculation)
Temperature dries left Humidificateur (humificator with vapor injection)
- ts = Dry temperature
in °C
- Hr = relative Humidity
- Hs = Specific moisture in kg/kg of dry air
- MassVol = Density in kg/m3 of humid air
- TempVap = Temperature of injection of the water vapor
- Z = Altitude en m
Fonction =Psy_th2(Ts, Hr, Hs, MassVol, TempVap, Z)
...... (iterative Calculation)
Iterative calculation = calculation is done by iteration, i.e.
successive approaches. The margin of error can be at 0.1°C.
at most
Last update:
|